← Resources
Guide

Hardening baselines for firewalls, switches and Windows hosts in OT

A practical starting baseline for the devices most sites run, and how to keep it from drifting.

The short answer

A baseline is the documented, approved configuration of a device: operating system or firmware, installed software, enabled ports and services, accounts and security patches. CIP-010 requires one per BES Cyber Asset at medium and high impact, authorized and documented changes, and an updated baseline within 30 days of a change; high impact systems must be monitored for changes at least every 35 days. CIP-007 sets the hardening: ports and services, patches, malicious code, logging and access control.

What a baseline is for

A baseline is the documented, approved configuration of a device: software and firmware versions, enabled services and ports, accounts, security patches applied and custom software. CIP-010 asks you to keep one per BES Cyber Asset and to authorize and document changes to it.

The point is not the document — it is being able to tell, at any time, whether a device still matches what you approved.

Firewalls

  • Management only from a dedicated management network or jump host; no management on outside interfaces.
  • Named administrator accounts with MFA where supported; disable or rename default accounts.
  • Log to a central collector (syslog) and keep time synchronized.
  • Back up the configuration after every approved change and compare it with the last known-good copy.

Switches and routers

  • Disable unused ports and place them in an unused VLAN; enable port security where the hardware supports it.
  • Turn off services you do not use (HTTP management, CDP/LLDP on edge ports, legacy protocols).
  • Use SNMPv3 with authentication and privacy; remove default community strings.
  • Send logs and SNMP traps to your collector.

Windows hosts (HMIs, engineering workstations, historians)

  • Remove software and roles the host does not need; disable unused services and listening ports (CIP-007 R1).
  • Apply security patches through an evaluated process with documented decisions (CIP-007 R2).
  • Use application allow-listing or anti-malware suited to the host's role (CIP-007 R3).
  • Enforce password and lockout settings; review accounts and remove those no longer needed (CIP-007 R5, CIP-004).
  • Forward security event logs centrally and retain them (CIP-007 R4).

Keeping it from drifting

Baselines drift through emergency fixes, vendor visits and forgotten tests. Compare live configuration with the approved baseline regularly — CIP-010 R2 requires monitoring for changes at least every 35 days for high-impact systems — and treat every unexplained difference as an event to investigate.

Common questions

What is a CIP-010 baseline?

The documented, approved configuration of a device: operating system or firmware, commercially available or open-source software installed, custom software, logical network accessible ports and security patches applied. CIP-010 R1 requires one per applicable Cyber Asset and authorized, documented changes to it.

How often must baselines be checked for drift?

CIP-010 R2 requires high impact systems to be monitored for changes to the baseline at least once every 35 calendar days. For other systems, regular comparison is good practice.

What does CIP-007 require for Windows hosts in OT?

Only needed ports and services (R1), security patches evaluated and applied through a documented process (R2), malicious code prevention (R3), security event logging (R4) and system access controls such as password and lockout settings (R5).

General guidance, not legal or compliance advice. Your obligations depend on your registration and assets — confirm them with your compliance team and Regional Entity.

From the blog