Recovery plans that actually work: what to back up, how often, how to test, and how to prove it.
CIP-009 requires recovery plans for BES Cyber Systems: the conditions that trigger them, the roles involved, how information needed for recovery is backed up, stored and verified, and how data is preserved for analysis. For high impact systems and medium impact systems at Control Centers, the plan must be exercised at least once every 15 calendar months, a representative sample of backups tested, and the plan updated within 90 days of a test or real recovery.
CIP-009 asks for recovery plans for BES Cyber Systems: the conditions that trigger them, the roles involved, how information needed for recovery is backed up and stored, how backups are verified, and how data is preserved for analysis.
Under CIP-009-6 the testing and update rules apply to high impact systems and to medium impact systems at Control Centers: exercise the plan at least once every 15 calendar months (operational exercise, tabletop or actual recovery), and test a representative sample of backups so you know they restore. High impact systems also need an operational exercise at least once every 36 calendar months. Within 90 days of a test or an actual recovery, update the plan with lessons learned and tell the people affected. For other systems the same routine is good practice even where CIP-009 does not require it.
Recovery plans for BES Cyber Systems that cover activation conditions, roles and responsibilities, backup and storage of information needed for recovery, verification of backups, and preservation of data for analysis.
For high impact systems and medium impact systems at Control Centers, at least once every 15 calendar months (operational exercise, tabletop or actual recovery), plus an operational exercise at least once every 36 calendar months for high impact systems. Update the plan within 90 days of a test or recovery.
Device configurations after every approved change, system images or rebuild procedures for HMIs, engineering workstations and servers, application project files and licenses, and the documentation needed under pressure, with at least one copy offline or in a separate zone.
General guidance, not legal or compliance advice. Your obligations depend on your registration and assets — confirm them with your compliance team and Regional Entity.
One NERC CIP and OT security point a day: short videos on YouTube, posts on LinkedIn, and the blog (also on dev.to and Hashnode).